Molded Case Circuit Breaker
Time:2017-07-20 09:46:35    Page view (511)
1 Overview
1.1 Scope of application
JCM1 series circuit breakers are mainly used for AC, undervoltage and short circuit protection for distributed power and protection lines and power supply in the distribution network with 50Hz-60Hz, rated insulation voltage 800V, rated working voltage 690V and below and rated current below 1250A , 400A frame type and below the circuit breaker can also be used as motor overload, under voltage and short circuit protection. Under normal circumstances can be used as a frequent conversion of the line and the motor is not frequent start.
This series of circuit breakers with small size, short circuit breaking capacity, arcing distance is small, anti-vibration characteristics, when the overload current or short-circuit current reaches or exceeds its specified value, the circuit breaker will automatically trip, cut off the power, device of.
1.2 circuit breaker model and meaning
 
Table 1 N-level type code
Table 2 tripping method and accessories code
Attachment name
Without attachments
Alarm contact
Divided contacts
Auxiliary contact
Undervoltage release
Exclusion
+
Auxiliary
Exclusion +
Undervoltage
Two groups of assistants
Auxiliary
+
Undervoltage
Exclusion
+
Call the police
Auxiliary + alarm
Undervoltage
+
Call the police
Excitation + auxiliary + alarm
Two groups of assistants
+
Call the police
Auxiliary
+
Undervoltage
+
Call the police
Instantaneous code
200
208
210
220
230
240
250
260
270
218
228
238
248
268
278
Duplicate code
300
308
310
320
330
340
350
360
370
318
328
338
348
368
378
Note 1: 200 denotes a circuit breaker main body with an electromagnetic trip, and 300 a circuit breaker body having a thermal and electromagnetic trip unit.
Note 2: But JCM1-100, JCM1-225 bipolar products only 210.310.220.320.230.330.
1.3 normal use, installation and transportation conditions
1.31 normal conditions of use
A) the ambient air temperature limit does not exceed +40 ℃, the lower limit of not less than -5 ℃, 24 hours within the average does not exceed +35 ℃;
B) the altitude of the installation site does not exceed 2000 m;
C) The relative humidity of the atmosphere shall not exceed 50% at the ambient maximum temperature of + 40 ° C and may have a relatively high relative humidity at a lower temperature (eg 90% at 20 ° C) and taking into account changes in temperature The condensation on the surface of the product;
1.3.2 Normal installation conditions
A) installation conditions: generally should be installed vertically, can also be installed horizontally (horizontal);
B) installation categories: circuit breaker main circuit Ⅲ; control circuit and auxiliary circuit for the class Ⅱ;
C) Pollution level: Level 3.
1.3.3 Normal storage and transportation conditions
A) the lower temperature limit of not less than -25 ℃, the upper limit is not higher than +55 ℃;
B) relative humidity (25 ℃) not more than 95%;
C) the product should be lightly transported during transport, should not be inverted, should try to avoid violent collision.
2 main technical parameters
Table 3 Main technical parameters
  
  model
Rated current
A
series
Power loss
Short-circuit breaking capacity KA (rms)
Ics / COS φ Icu / COSΦ
Arc distance
Fixed type
400V 690V
400V 690V
50mm
100mm
JCM1-63L
10,16,20,25,30,32,40,50,63
3
20
25
18 / 0.3 -
25 / 0.25 -
JCM1-63M
25
30
30 / 0.25
-
50 / 0.25
-
JCM1-63
4
33
  -
JCM1-100L
10,16,20,25,30,32,40,50,63,80,100
3
35
40
26 / 0.25
-
30 / 0.25
-
JCM1-100M
40
50
30 / 0.25
10 / 0.5
50 / 0.25
20 / 0.3
JCM1-100H
43 / 0.25
10 / 0.5
85 / 0.25
20 / 0.3
JCM1-100
2/4
26/35
-
30 / 0.25
10 / 0.5
50 / 0.25
20 / 0.25
JCM1-225L
100, 125, 160, 180, 200,
3
55
65
26 / 0.25
-
35 / 0.25
-
JCM, 1-225M
60
75
30 / 0.25
10 / 0.5
50 / 0.25
20 / 0.3
JCM1-225H
43 / 0.25
10 / 0.25
85 / 0.25
20 / 0.3
JCM1-225
2/4
40/80
-
30 / 0.25
10 / 0.25
50 / 0.25
20 / 0.3
JCM1-400C
200,225,250,315,350,400
3
80
100
20 / 0.25
-
35 / 0.25
-
JCM1-400L
30 / 0.25
-
50 / 0.25
-
JCM1-400M
90
110
40 / 0.25
-
70 / 0.25
-
JCM1-400H
50 / 0.25
-
100 / 0.2
-
JCM1-400
4
120
-
20 / 0.25
-
35 / 0.25
-
JCM1-630L
400
500
630
3
130
150
180
200
34 / 0.25
-
45 / 0.25
-
JCM1-630M
42 / 0.25
10 / 0.5
65 / 0.25
20 / 0.3
JCM1-630
4,
200
-
42 / 0.25
10 / 0.5
65 / 0.25
20 / 0.3
2.1.1 The main technical parameters of the control circuit
  The sum of the power supply voltage (Us) and the undervoltage release factor (Ue) of the shunt release and the motor mechanism are shown in Table 4.
Table 4 The main technical parameters of the control circuit
The same time as
 Category
Rated operating voltage
AC 50Hz
DC
Release
Shunt release
Us
230,400
24,110,220
Undervoltage release
Us
230,400
-
Motor mechanism
Us
230,400
24,110,220
2.1.2 auxiliary circuit main technical parameters
The main technical parameters of auxiliary contacts and alarm contacts are shown in Table 5
Table 5 auxiliary contact and alarm contact the main technical parameters
Agreed to heat
Current Ith A
Amount of insulation
Voltage Ui V
The amount of working voltage Ie A
Applicable shell level
Maximum rated current
AC400V
DC220V
3
400
0.26
0.15
225A
0.4
0.2
400A and below
2.2 Main technical performance
2.2.1 circuit breaker short circuit protection current setting value in Table 6
Table 6 Short circuit protection current setting value
Rated current In A
For power distribution protection
Protection of motor
Set the value of the correctness
Agreed time S
In≤400
10 In
12In
± 20%
<0.2 trip
400 & lt; In & lt;
-
630 <In? 1250
7 In
-
Note: users need special setting value, the manufacturer can contact the special enough.
2.2.2 Distribution circuit breaker anti-time disconnection characteristics in Table 7
Table 7 Circuit breaker anti-time break characteristics
Experiment name
Current rectification
Multiple magnification
Agreed time T
Start
status
Benchmark
temperature
In ≤ 63A
63A <In? 225A
In> 225A
Agreed not to take off
Buckle current
1.05 In
≥1h
≥2h
Cold state
+ 30 ° C
Conventional trip current
1.3 In
<1h
<2h
Hot state
Can return time
3.0 In
5s
8s
12s
Cold state
2.2.3 Motor protection circuit breaker anti-time disconnection characteristics in Table 8
Table 8 Circuit breaker anti-time disconnection characteristics for motor protection
Experiment name
Current rectification
Multiple magnification
Agreed time T
Start
status
Benchmark
temperature
In≤100A
100A <In? 400A
It is agreed that no current will be tripped
1.00 In
≥2h
Cold state
+ 40 ° C
Conventional trip current
1.20In
<2h
Hot state
1.50In
≤2min
≤ 4min
Hot state
Can return time
7.20In
2s <Tp≤10s
4s <Tp≤10s
Cold state
2.2.4 Operating performance of the circuit breaker The number of operating cycles is shown in Table 9
Table 9 Number of operating cycles of the circuit breaker
Shell the largest level
Rated current
Hourly operation
Cycles
Number of operating cycles
Current
No current
Total number of times
JCM1-63
120
1500
8500
10000
JCM1-100
120
1500
8500
10000
JCM1-225
120
1000
7000
8000
JCM1-400
60
1000
4000
5000
JCM1-630
60
1000
4000
5000
JCM1-800
20
500
2500
3000
  
2.3 Electric control When the circuit breaker is closed or disconnected, its action value
A) When the circuit breaker is operated with an electric operating mechanism, at any voltage between the control power supply voltage of 85% to 110%
Should be able to ensure that the circuit breaker in the no-load and the amount of short-circuit connection between the reliable closure;
B) Shunt release can be reliably operated at any voltage between 70% and 110% of the line control supply voltage;
C) undervoltage release in the amount of operating voltage range of 70% to 35%, the release should be activated.
3 Outline and mounting dimensions
3.1 Molded Case Circuit Breaker Front Wiring Board Wiring and Outline Dimensions are shown in Table 10

Circuit Breaker Installation Size:

 

4 Ordering Information

   1, the product model, name; 2, the number of poles; 3, rated current; 4, the rated residual operating current; 5, the number of orders.

   For example: JCM1-100L / 3300 100A only 10.